Electrician’s Discussion

We met today to discuss the changes needed in the electrical work. The inspector gave us a 2 hour time frame and came about 10 minutes after it was over. So the project manager and I had a nice chat in the living room for two hours while waiting.
While we were waiting I went over what I understood the inspector to say at the inspection and I was mostly on target with a few mistakes and omissions. Here is the list as I remember it after listening again.

1. Some studs have holes for the wire that are closer than 1 1/4″ to the edge of the stud and these need metal plates. (I counted about 16 places.)
2. Where wires are within a 1 1/2″ chase they need to be stapled 1 1/4″ away from the studs. Using a different kind of staple will take care of that. (2 places in master bedroom/bath)
3. Where wires are exposed in the ceiling they will have to be changed to steel armored and must run 1 1/4″ away from the furring strips. Screwing through to the stud with a different kind of clip will take care of that. Boxes will have to be changed to accept the metal clamp connectors for these wires. (There are four ceiling fixtures and one outlet supply line that need to be replaced.)
4. The wood boiler supply wire will need to be placed in armored cable.
5. The wire mold stubs will need wiring ends. Home Depot does not carry these so I ordered two from Amazon.
6. In the ceiling chase, the wires that touch the old gas pipe need to be separated from the pipe with ties and insulation.

Otherwise the inspector said that they were a good company and it looked like a good job. Just a few things that they don’t run into every day that can’t pass. So with some electrical talk going on about NM wire and P Clips or whatever, they were able to come to a decision.

I really didn’t want the guy who had argued with me back so I asked the project manager if I could get the work done by the guy who came just one day whose work looked nice and neat. He said he would send the same helper with him. I may have to wait longer for this team but he will call me tomorrow to let me know what their schedule will be.

I need to be ready for drywall and get that put in soon as the electrical inspector can’t do the final inspection until it is drywalled and painted. So I better get moving on the membrane and the ventilation chase so it is ready for drywall.